Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 85

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Basic Operating Procedure
Protocol Macro
Executing Flag
Input condition
191915
56
Communications Port
Enabled Flag for Port 7
A20207
PMCR(260)
C1
C2
S
D
ER
FAL (006) 01
If the input condition turns ON when the Protocol Macro Executing Flag
(CIO 191915 for port 2) is OFF and the Communications Port Enabled
Flag (A20207 for internal logic port, communications port 7) is ON, com-
munications sequence No. 100 registered in the Serial Communications
Board is called, and data is sent and received via port 2 of the Serial Com-
munications Board.
The amount of send data depends on the number of words specified in
D00000 (the number of words after D00001 plus 1 for D00000 itself), and
is sent from the next word after D00001.
Number of words
S:D00000
D00001
The receive data is stored in consecutive words beginning with D00011,
and the number of words actually stored in D00010 (the number of words
after D00011 plus 1 for D00010 itself) is stored.
Number of words
S:D00000
D00011
Receive data
c. Execute PMCR(260)
4. For details on the confirming operation, see Section 12 Tracing and I/O
Memory Monitoring.
• Transmission Line Tracing
The data in the send/receive messages flowing over the transmission
line (RS-232C or RS-422A/485) and the control codes are traced.
• I/O Memory Monitoring
Monitors send/receive data and the status of the various flags.
1:N NT Links
Refer to the user's manual for the PT.
Serial Gateway Mode
• Sending FINS commands from the PLC
Send FINS commands using the CMND(490) instruction. For details, refer
to 6-8-5 Sending Commands Using the CMND(490) Instruction.
• Sending FINS commands from the PT
Execute the PT's SAP (Smart Active Parts) library.
• Sending FINS commands from a Programming Device that uses CX-
Server as the communications driver, such as the CX-Programmer.
Communications port 7 and serial port 2
Destination unit address E1: Serial Communications Board
#72E1
#0064
Sequence No. 100
First word of send data
D00000
First storage word for receive data
D00010
Number of send words plus 1 for D00000
Send data
Number of words
Number of send words plus 1 for D00010
Number of words
Section 1-9