Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 580

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ J Temperature Controller Protocol
Read Parameters 1 (Sequence No. 208 (Hex 00D0))
Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and
stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
+0
Number of send data words
+1
Number of units
+2
(Undefined)
~
+26
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
2nd unit
Unit No. (2 digits BCD)
+26
25th unit
(max.)
Unit No. (2 digits BCD)
+0
Number of receive data words
+1
Set point
+2
Alarm value 1
+3
Alarm value 2
Heater burnout alarm value
+4
~
+97
Set point
+98
Alarm value 1
+99
Alarm value 2
+100
Heater burnout alarm value
Unit No.
~
(max.)
Unit No.
Number of units + 2
0001 to 0019 (1 to 25 decimal)
00 to 31
00 to 31
00 to 31
1st unit
~
25th unit (max.)
Appendix J
Data
551