E5ZE Temperature Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Ramp Value (Sequence No. 164 (Hex 00A4))
Writes the ramp values.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Manual Output Value (Sequence No. 165 (Hex 00A5))
Writes the manual output values for control output in manual operation.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
534
Number of send data words
+0
+1
(Undefined)
+2
(Undefined)
+3
Time unit
+4
(Undefined)
+5
Time unit
~
+16
(Undefined)
Time unit
+17
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Ramp value (3 digits BCD)
+3
Channel 0
Time unit (one ASCII character)
+4
Channel 1
Ramp value (3 digits BCD)
+5
Channel 1
Time unit (one ASCII character)
+16
Channel 7
Ramp value (3 digits BCD)
+17
Channel 7
Time unit (one ASCII character)
Number of send data words
(Undefined)
Output value
Cooling output value
Output value
Cooling output value
Output value
Cooling output value
Unit No.
Ramp value
(Undefined)
Ramp value
(Undefined)
Ramp value
(Undefined)
0012 (0018 decimal) (fixed)
00 to 0F
000 to 999
S: Seconds; M: Minutes; H: Hours
000 to 999
S: Second M: Minute H: Hour
•
•
•
000 to 999
S: Seconds; M: Minutes; H: Hours
Unit No.
Channel 0
Channel 1
~
Channel 7
Appendix I
Channel 0
Channel 1
~
Channel 7
Data