Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 200

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Auxiliary Area and CIO Area Allocations
Words
Boards
(CS Series Only)
(CS/CJ Series)
Port 1
Port 2
Port 1
CIO
CIO
n + 11
1911
1921
CIO
CIO
n + 12
1912
1922
CIO
CIO
n + 13
1913
1923
CIO
CIO
n + 14
1914
1924
Bit
15 14 13 12 11 10 09 08 07 06 05 04 03
CIO 1909 (port 1) or
CIO 1919 (port 2)
n + 9 (port 1) or
n + 19 (port 2)
Bit
Unit
Port 2
n + 21
15 to 12
11 to 08
07 to 04
03 to 00
n + 22
15 to 00
n + 23
15 to 00
n + 24
15 to 08
07 to 00
Note When the repeat counter is used to read words and 0 is read, 0 will be stored
and the step will be skipped.
0
0
Serial Gateway Prohibit Flag
(protocol macro)
Sequence Wait Flag
Sequence Abort Completion Flag
Sequence End Completion Flag
Tracing Flag
Abort Flag
Step Error Processing Flag
Protocol Macro Executing Flag
Setting contents
Reserved
Executed Step No. (code)
0 to 15 (0 to F hex)
Reserved
Executed Reception Case No. (code)
0 to 15 (0 to F hex)
Executed Reception Case No. Flag
No. 0 to 15: Correspond to bits 00 to 15
Executed Step No. Flag
No. 0 to 15: Correspond to bits 00 to 15
Repeat Counter Setting Value
1 to 255 (01 to FF hex) (see note)
Repeat Counter Present Value
1 to 255 (01 to FF hex) (see note)
02
01 00
0
0
Error code
Section 5-3
1: Prohibited
0: Not prohibited
1: Sequence wait status
0: Other than above
1: Sequence aborted
0: Other than above
1: Sequence ended
0: Other than above
1: Trace executing
0: Other than above
1: Protocol macro processing aborted
0: Other than above
1: Step processing error
0: Step processing normal
1: Protocol macro executing
0: Protocol macro executed
171

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents