Cable Connections

CPU Rack
(CS1W-BC103, CS1W-BC083, CS1W-BC053, CS1W-BC033, CS1W-BC023)
2/3/5/8/10 slots
CS-series Expansion Racks
(CS1W-BI108, CS1W-BI083, CS1W-BI053, CS1W-BI033)
3/5/8/10 slots
C200H Expansion Rack
Note
2-4

Cable Connections

2-4-1

Coaxial Units

Required Components
1,2,3...
CPU Rack
SYSMAC LINK Units can be mounted to the
2/3/5/8/10 slots shown in the diagram on the right.
CS1 Expansion Rack
SYSMAC LINK Units can be mounted to the
3/5/8/10 slots shown in the diagram on the right.
C200H Expansion I/O Rack
SYSMAC LINK Units cannot be
mounted to Expansion I/O slots.
Up to 16 CPU Bus Units may be installed to on PLC.
SYSMAC LINK Units can be connected with either coaxial cable or optical
fiber cable. This section describes the procedures required to connect these
cables.
This section describes the procedures required to connect SYSMAC LINK
Units with coaxial cables.
1. Coaxial cable and Connectors:
Use the 5C-2V coaxial cable designed for indoor use. Install connectors on
each end of the cable. Cables must be continuous. No intervening cable
connectors or breaks are permitted. OMRON recommends the following
cables and connectors.
2. F Adapters (C1000H-CE001):
Coaxial cables are connected to the SYSMAC LINK Units via F Adapters.
One F Adapter is included as an accessory with SYSMAC LINK Units that
use coaxial cables (CV500-SLK21).
3. Terminator (C1000H-TER01):
Two Terminator units (sold separately) are required, one for the F Adapter
at each end of the network.
Section 2-4
Mount to up to four
of these slots.
PS:
Power Supply Unit
CPU: CPU Unit
19