Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 83

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Basic Operating Procedure
Protocol Macro
Executing Flag
Input condition
191915
54
Refer to information on the 3rd operand of PMCR(260) in Appendix B
CompoWay/F Master Protocol and set the number of send data words in
S, and set the send data starting in S+1.
2. Coding PMCR(260)
Example:
The following example shows how to use a Serial Communications Board
to read the present value for a K3N-series Digital Panel Meter using the
CompoWay/F Master standard system protocol sequence No. 600:
Send/receive with ASCII conversion and response.
Communications Port
Enabled Flag for Port 7
A20207
PMCR(260) (260)
C1
C2
S
D
ER
FAL (006) 01
If the input condition turns ON when the Protocol Macro Executing Flag
(CIO 191915 for Port 2) is OFF and the Communications Port Enabled
Flag (A20207: Internal logic port, communications port 7) is ON, commu-
nications sequence No. 600 of the standard system protocol in the Serial
Communications Board is called, and data is sent and received via port 2
of the Serial Communications Board.
Send Data
0007
S:D00000
D00001
0000
D00002
0101
D00003
000C
D00004
C000
D00005
0000
D00006
0001
Receive Data
D:D00010
0004
D00011
D00012
D00013
3. Executing the PMCR(260) Instruction
4. For details on confirming operation, see Section 12 Tracing and I/O Mem-
ory Monitoring in the CX-Protocol Operation Manual (W344).
• Transmission Line Tracing
The data in the send/receive messages flowing over the transmission
line (RS-232C or RS-422A/485) and the control codes are traced.
• I/O Memory Monitoring
Monitors send/receive data and the status of the various flags.
Communications port 7 and serial port 2
Destination unit address E1: Serial Communications Board
#72E1
#0258
Sequence No. 600
D00000
First word of send data
D00010
First storage word for receive data
7 words from D00000 to D00006
K3N node No. : 00
CompoWay/F command "0101" (reads the K3N present value)
Number of send bytes
CompoWay/F command send data
(Variable type, read start address, 00, number of elements)
4 words from D00010 to D00013
Response code is stored.
The read data (in this case, the present value of K3N) is stored.
Section 1-9