Soldering - Omron SYSMAC CS1W-SCB41-V1 Operation Manual

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

RS-232C and RS-422A/485 Wiring
Shield Not Connected to Hood (FG)
1,2,3...
3-4-4

Soldering

1,2,3...
5. Fold back the braided shield.
6. Wrap aluminum foil tape around the folded shield.
1. Cut the cable to the required length.
2. Remove the specified length of the sheath from the cable using a knife. Be
careful not to scratch the braided shield.
25 mm (RS-422A)
40 mm (RS-232C)
3. Trim off all the braided shield using scissors.
4. Remove the insulation from each conductor using a stripper so that the ex-
posed conductor length is 5 mm.
5 mm
5. Wrap adhesive tape around the conductor from which the braided shield
was removed.
1. Thread a heat-shrinking tube through each conductor.
2. Temporarily solder each conductor to the corresponding connector termi-
nals.
3. Completely solder each conductor.
Section 3-4
Aluminum foil tape
Adhesive tape
119

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents