Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 520

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

E5 @ K Digital Controller Write Protocol
Write Input Digital Filter (Sequence No. 062 (Hex 003E))
Writes the input digital filter.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Alarm Hysteresis (Sequence No. 063 (Hex 003F))
Writes the alarm 1 hysteresis and alarm 2 hysteresis.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Input Shift Value (Sequence No. 064 (Hex 0040))
Writes the input shift upper limit and input shift lower limit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
+0
Number of send data words
+1
(Undefined)
+2
Input digital filter
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Input digital filter (4 digits BCD)
Number of send data words
+0
+1
(Undefined)
Unit No.
Alarm 1 hysteresis
+2
+3
Alarm 2 hysteresis
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Alarm 1 hysteresis
(4 digits BCD)
+3
Alarm 2 hysteresis
(4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
Input shift upper limit
+3
Input shift lower limit
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits BCD)
+2
Input shift upper limit (4 digits BCD)
+3
Input shift lower limit (4 digits BCD)
Unit No.
0003 (fixed)
00 to 31
0000 to 9999
0004 (fixed)
00 to 31
0001 to 9999
0001 to 9999
Unit No.
0004 (fixed)
00 to 31
0000 to 9999
0000 to 9999
Appendix G
Data
Data
Data
491