Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 282

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Allocation DM Area for No-protocol Mode
Serial Communications Boards (CS Series only)
Serial Communications Units (CS/CJ Series)
Setup Area Contents
Words
Board
(CS Series only)
(CS/CJ Series)
Port 1
Port 2
Port 1
D32000
D32010
m
Setup Area Allocated in the DM Area: D32000 to D32099
Words
D32000 to D32005
D32010 to D32015
D32006 to D32009
D32016 to D32019
D32020 to D32767
Setup Area Allocated in the DM Area: D30000 to D31599
First Word in Setup Area Allocated in the DM Area:
m = D30000 + 100 × unit number
Unit No.
Unit No. 0
D30000 to D30099
Unit No. 1
D30100 to D30199
Unit No. 2
D30200 to D30299
Unit No. 3
D30300 to D30399
Unit No. 4
D30400 to D30499
Unit No. 5
D30500 to D30599
Unit No. 6
D30600 to D30699
Unit No. 7
D30700 to D30799
Unit No. 8
D30800 to D30899
Unit No. 9
D30900 to D30999
Unit No. A
D31000 to D31099
Unit No. B
D31100 to D31199
Unit No. C
D31200 to D31299
Unit No. D
D31300 to D31399
Unit No. E
D31400 to D31499
Unit No. F
D31500 to D31599
Bit
Unit
Port 2
m+10
15
Port settings
12 to 14 Reserved
08 to 11 Serial communications mode
3: No-protocol
05 to 07 Reserved
04
Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
03
Data length
02
Stop bits
01
Parity
00
Parity
Usage
Port 1 Settings
Port 2 Settings
Not used in no-protocol mode
Reserved for the system
Words
m to m+5: Port 1 Settings
m+10 to m+15: Port 2 Settings
m+6 to m+9, m+16 to m+19: Not used.
m+20 to m+99: Not used.
Setting contents
0: Defaults; 1: User settings
0: 7 bits; 1: 8 bits
0: 2 bits; 1: 1 bit
0: Yes; 1: No
0: Even; 1: Odd
Section 7-2
m = D30000 + 100 × Unit No
253

Hide quick links:

Advertisement

Table of Contents
loading