Omron SYSMAC CS1W-SCB41-V1 Operation Manual page 462

Sysmac cs series; sysmac cj series. serial communications boards and serial communications units
Table of Contents

Advertisement

Host Link FINS Command Master
MEMORY AREA FILL
(Sequence No. 760 (Hex 02F8))
This sequence sends command code 0102 hex to the specified Host Link Unit and writes data to consecutive
I/O memory area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
+0
Number of send data words
First word of
send data
Host Link unit number
+1
Remote destination node
+2
address
+3 Memory area code
+4
First write address
+5
Number of write data bytes
+6
Write data
Offset
Contents (data format)
+0
Number of send data words
(4 digits hex)
+1
Host Link unit
No.
(2 digits BCD)
+2
Remote destina-
tion node
address (DA1)
(2 digits hex)
+3
Memory area
code
(2 digits hex)
First write address (6 digits hex)
+4
Number of write elements
+5
(4 digits hex)
Write data (4 digits hex)
+6
Number of receive data words
+0
Receive data
storage words
+1
End code
Offset
Contents (data format)
+0
Number of receive data words
(4 digits hex)
+1
End code (4 digits hex)
Remote destination
network address
Remote destination
unit address
Always 0007 hex (7 decimal)
Remote destina-
Host Link unit number: 00 to 31
tion network
Remote destination network address
address (DNA)
(DNA): 00 to 7F hex
(2 digits hex)
Remote destina-
Remote destination node address
tion unit address
(DA1): 00 to FE hex
(DA2)
Remote destination unit address (DA2):
(2 digits hex)
00 to FE hex
Specify the memory area (2 digits hex)
and the first write address (2 digits hex)
Specify the number of write elements.
Specify the write data.
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
Appendix D
Data
Data
433

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents