YASKAWA SGD7S series Product Manual page 176

Sigma-7s servopack with ft/ex specification for cutting application feed shaft motor
Hide thumbs Also See for SGD7S series:
Table of Contents

Advertisement

Alarm Number:
Possible Cause
Alarm Name
The surrounding air
temperature around
the Servomotor is too
A.860:
high.
Encoder Over-
heated
The Servomotor load
(Detected when a
is greater than the
Rotary Servomo-
rated load.
tor, Absolute Lin-
ear Encoder, or
Direct Drive Ser-
vomotor is con-
nected. However,
A failure occurred in
this alarm is not
the encoder.
detected for
SGMCS
Servomotors with
Incremental
Encoders.)
(Detected at the
A failure occurred in
encoder.)
the SERVOPACK.
The surrounding tem-
perature around the
Servomotor is too
high.
The motor load is
greater than the rated
load.
A.861:
Motor Over-
A failure occurred in
heated
the Serial Converter
Unit.
A failure occurred in
the SERVOPACK.
A.890:
A failure occurred in
Encoder Scale
the linear encoder.
Error
A.891:
A failure occurred in
Encoder Module
the linear encoder.
Error
Setting the origin of
the absolute linear
encoder failed
A.8A0:
because the motor
External Encoder
moved.
Error
A failure occurred in
the external encoder.
Confirmation
Reduce the surrounding
Measure the surround-
air temperature of the
ing air temperature
Servomotor to 40°C or
around the Servomotor.
less.
Operate the Servo Drive
Use the accumulated
so that the motor load
load ratio to check the
remains within the speci-
load.
fied range.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the Servomotor or
absolute linear encoder
may be faulty. Replace the
Servomotor or absolute
linear encoder.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the SERVOPACK
may be faulty. Replace the
SERVOPACK.
Measure the surround-
Reduce the surrounding
ing temperature around
air temperature of the
the Servomotor.
Servomotor to 40° or less.
Check the load with the
Operate the Servo Drive
accumulated load ratio
so that the motor load
on the Motion Monitor
remains within the speci-
Tab Page on the Sig-
fied range.
maWin+.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the Serial Con-
verter Unit may be faulty.
Replace the Serial Con-
verter Unit.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the SERVOPACK
may be faulty. Replace the
SERVOPACK.
The linear encoder may
be faulty. Replace the lin-
ear encoder.
Turn the power supply to
the SERVOPACK OFF and
ON again. If an alarm still
occurs, the linear encoder
may be faulty. Replace the
linear encoder.
Before you set the ori-
gin, use the fully-closed
The motor must be
feedback pulse counter
stopped while setting the
to confirm that the
origin position.
motor is not moving.
Replace the external
encoder.
9.1 Alarm Displays
9.1.2 Troubleshooting Alarms
Continued from previous page.
Correction
Reference
page 8-2
page 8-2
*1
Continued on next page.
9
9-23

Advertisement

Table of Contents
loading

Table of Contents