Show/Hide Bookmarks
6.1.4
6.2
6.2.1
L
Actual value display via codes
You can read different actual values using the following codes:
Code
Meaning
C0051
Absolute actual speed [rpm]
C0052
Absolute motor voltage [V]
C0053
Absolute DC bus voltage [V]
C0054
Absolute motor current [A]
C0060
Rotor position [Inc/rev]
C0061
Heatsink temperature [°C]
C0063
Absolute motor temperature [°C]
Display only if the KTY (PTC) is connected via X7 or X8.
C0064
Controller load [%]
Identification
•
You can read the software version of the controller under C0099.
•
C0093 indicates the controller type.
Information on operation
When operating the controller, please observe the following notes:
Stop!
•
Cyclic connection and disconnection of the controller supply voltage at L1, L2, L3 or +U
-U
may overload the internal input current limitation:
G
– Allow at least 3 minutes between disconnection and reconnection.
•
During mains switching (L1,L2,L3) it is not important whether further controllers are supplied
via the DC bus.
Switching on the motor side
•
Switching on the motor side of the inverter is permissible for emergency switch-off.
•
Please note:
– Switching while a controller is enabled may cause the fault message "OCx"
(short-circuit/earth fault in operating mode x).
– For long motor cables and operation of controllers with smaller output power, leakage
currents through interfering cable capacitances may cause the fault message "OCx".
– Switching equipment on the motor side must be dimensioned for DC voltages
(U
= 800 V).
DC max
During operation
EDSVS9332P-C EN 3.0
,
G
6-3