Function library
7.5.8.6

Homing mode 4 and 5

Purpose
Simple homing in all positioning modes (C1210 = 0, 1, 2).
The homing switch (POS-REF-MARK) will not be overridden. Positions to the right of the
homing switch cannot occur due to the mechanical design.
The homing switch must be in direction of the movement.
Move to homing switch, reverse and move to reference point
Mode 4: Traversing direction to the positive end of the travel range limit switch
Set C1213 = 4.
Fig. 7-24
Move to POS-REF-MARK, reverse and move to reference point
Function procedure
Move towards travel range limit switch with homing speed C1242 up to homing switch (case
).
Reverse there and move to the reference point. The homing switch must be assigned during
the entire homing process!
The reference point is at the first zero pulse / zero position of the position encoder after leaving
the homing switch.
If the drive is already positioned on the homing switch before homing it is reversed
immediately
(case ).
Mode 5: Traversing direction to negative end of travel range limit switch
Set C1213 = 5.
Function procedure
Like mode 4, but the drive traverses in negative direction of travel range limit switch.
7-54