5.5

Switch on PC, start GDC

Switch on PC.
Start the GDC program under Windows.
When GDC is in "online operation"
The "Find LECOM A/B drives" dialog box is opened.
Click "Find". GDC will now search for a controller.
GDC selects the first controller found.
GDC tests all baud rates which can be set.
GDC loads the parameter set description for the connected controller.
– If GDC does not find a parameter set description, you are asked which description you
want to load alternatively.
GDC automatically reads the parameter set from the controller.
When GDC is in "offline operation"
You have to select the controller manually.
– You can change to "online operation". GDC automatically selects a controller.
Open the "Controller" menu in the menu bar and click "Select". Make your choice for:
– the desired parameter set description.
– Baud rate.
– Controller address.
5-6