Phase controller

The phase controller is required to achieve phase synchronisation and driftfree standstill.
Tip!
Select a configuration with digital frequency coupling in C0005 since this serves to link all important
signals automatically. On this basis the system can be optimised.
Activating the phase controller
1. Configure a signal source with C0894, which provides the phase difference between set and
actual phase (see "Digital frequency configuration under C0005).
2. Select a value > 0 at the MCTRL-PHI-LIM input.
3. Trigger the input MCTRL-PHI-ON with HIGH (e.g. with FIXED1).
4. Set gain of the phase controller C0254 > 0 (see chapter 7.5.60.4)
– Before setting C0254, select a P-gain C0070 of the n-controller as high as possible.
– Increase C0254 during operation until the drive shows the required control response.
Influence of phase controller
The output of the phase controller is added to the speed setpoint.
If the actual phase is lagging, the drive is accelerated
If the actual phase is leading the drive is decelerated until the required phase synchronisation
is achieved.
The influence of the phase controller consists of:
Phase difference multiplied by the P-gain C0254
Additional influence via analog signal at MCTRL-P-ADAPT
Limitation of the phase controller output to ±MCTRL-PHI-LIM
Limitation of the phase controller output
This limits the max. speed-up of the drive at high phase differences.