Freely Assignable Digital Inputs (Digin) - Lenze 9300 System Manual

Servo position controller
Hide thumbs Also See for 9300:
Table of Contents

Advertisement

Show/Hide Bookmarks
Function library
7.5.48

Freely assignable digital inputs (DIGIN)

Purpose
Reading and conditioning of the signals at the terminals X5/E1 to X5/E5.
Fig. 7-147
Freely assignable digital inputs (DIGIN)
Name
DIGIN-CINH
DIGIN1
DIGIN2
DIGIN3
DIGIN4
DIGIN5
Function
The terminals X5/E1 to X5/E5 are scanned every millisecond. The level for every input can be
inverted. For this, proceed as follows:
Select code C0114 with corresponding subcode (e.g. subcode 3 for input X5/E3)
Enter the desired level as a parameter:
– 0 = Level not inverted (HIGH active)
– 1 = Level inverted (LOW active)
7-192
DIGIN
X5
28
E1
C0114/1...5
E2
E3
1
E4
E5
Signal
Type
DIS
DIS format
d
-
dec
d
C0443
dec
d
C0443
dec
d
C0443
dec
d
C0443
dec
d
C0443
dec
EDSVS9332P-D21 EN 3.0
DCTRL -X5/28
DIGIN-CINH
DIGIN1
DIGIN2
DIGIN3
0
DIGIN4
1
DIGIN5
C0443
Source
CFG
List
Lenze
-
-
-
Controller inhibit acts directly on the DCTRL
control
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Note
L

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents