Function library
7.5.13.6
Set position value
Purpose
Shifting of the real measuring system during program processing
Fig. 7-39
Set position value
Function
Selection of the function "Set position value" in PS under PS mode (C1311=5).
The position setpoint (POS-SETPOS) is set to the target position selected in the PS.
The actual position value (POS-ACTPOS) is set in order to keep the actual following error (no
jerk).
Setting the position value shifts the real zero; the actual reference offset (C1220/7) is changed.
The actual reference offset does not correspond to the input value under C1225 anymore.
The real zero can be shifted within the position limiting values (C1223, C1224). When
exceeding these limits the error message "P08" (actual offset out of range) is set.
7-84
EDSVS9332P-D21 EN 3.0
R e a l
m e a s u r i n g
s y s t e m
M a c h i n e
m e a s u r i n g
s y s t e m
9300POS012