For U.s. Only: Ac Outlet - Siemens HiPath 5000 Service Manual

Hide thumbs Also See for HiPath 5000:
Table of Contents

Advertisement

inst_h3.fm
Installing HiPath 3000
Installing HiPath 3800
4.2.3.1.1

For U.S. only: AC outlet

An AC connection is required for each cabinet. The AC connection must fulfill the requirements
specified in Table 4-2.
Table 4-2
Electrical Connection Values (USA only)
Nominal
Nominal voltage range
voltage
from
120 V AC/
110 V AC
60 Hz
WARNING
7
Never connect a HiPath 3800 system or a combination of HiPath 3800 systems di-
rectly to a wall socket. Use a UL-listed or CSA-certified surge protector for every two
cabinets.
AC Power Outlet Requirements
A UL-listed or CSA-certified surge protector must be connected between the socket and
the system. Two cabinets can be connected to each surge protector. Never connect a Hi-
Path 3800 system or a combination of systems directly to a wall socket.
The power source may not be more than 2.4 m (8 ft.) from the system.
The power source must provide 120 V AC (single-phase, fused) power at 50-60 Hz and
20 A.
A warning should be attached to the circuit breaker to prevent accidental removal of power.
An independent electric circuit with an isolated ground conductor should be used.
The system must be properly grounded before startup (see description in Section 4.2.3.4).
4-6
Nominal Frequency
to
from
130 V AC
47 Hz
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
Wall Outlet Configura-
Range
to
63 Hz
NEMA 5-15, 2-pin, 3-
wire, earth
P31003-H3560-S403-54-7620, 09/05
tions

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hipath 3000Hipath 3800

Table of Contents