inst_h3.fm
Installing HiPath 3000
Installing HiPath 3750, HiPath 3700
4.3.3.8.1
For U.S. only: Connecting Network Facilities
DANGER
7
Ground the system properly before connecting the stations.
Connecting to the Point of Demarcation
Most main distribution frames are designed with a network demarcation block. You must cross-
connect the MDF to the incoming trunks. Use a standard wiring tool for laying the cable wires.
Connecting to T1, PRI, or CorNet
Caution
7
The TMST1 module can only be installed in conjunction with a listed channel service
unit (CSU).
Secondary Protection
DANGER
7
To protect against surge voltage caused by lightning, the following boards require
secondary protection when their lines leave the building where the main distribution
frame is housed:
SLA16N / SLA24N
●
TIEL4*
●
TMDID8
●
TMGL8
●
TMST1**
●
* If not connected to facility provider terminal equipment.
** When this module is connected to the public network, secondary protection must
be provided by the CSU.
4-128
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
P31003-H3560-S403-54-7620, 09/05