8. SUPPLEMENTARY INFORMATION

8. SUPPLEMENTARY INFORMATION

8.1

Application Example

Setup procedure for a simple application
Motor:
Application requirements:
Inverter used:
Settings:
This application is now to be modified as follows:
Operation of motor up to 75 Hz
(voltage/frequency curve is linear up to 50 Hz).
Motor potentiometer setpoint in addition to
analogue setpoint .
Use of analogue setpoint at maximum 10 Hz.
Ramp times to remain the same.
Parameter adjustments:
8.2

USS Status Codes

The following list gives the meaning of status codes displayed on the front panel of the inverter when the serial
link is in use and parameter P001 is set to 006:
001
Message OK
002
Slave address received
100
Invalid start character
101
Timeout
102
Checksum error
103
Incorrect message length
104
Parity fail
Notes
(1)
The display flashes whenever a byte is received, thus giving a basic indication that a serial link
connection is established.
(2)
If '100' flashes on the display continuously, this usually indicates a bus termination fault.
© Siemens plc 1999
220 V
1.5 kW output power
Setpoint adjustable via potentiometer 0 - 50 Hz
Ramp up from 0 to 50 Hz in 15 seconds
Ramp down from 50 to 0 Hz in 20 seconds
MM150 (6SE9216-8BB40)
P009 = 2 (all parameters can be altered)
P081 - P085 = values given on motor rating plate
P006 = 1 (analogue input)
P002 = 15 (ramp up time)
P003 = 20 (ramp down time)
P009 = 2 (all parameters can be altered)
P013 = 75 (maximum motor frequency in Hz)
P006 = 2 (setpoint via motor potentiometer or fixed setpoint)
P024 = 1 (analogue setpoint is added)
P022 = 10 (maximum analogue setpoint at 10 V = 10 Hz)
V
220
43
English
50
75
f (Hz)
G85139-H1750-U049-C1
19/08/99