Setting Application Macros - Siemens SINAMICS V20 Series Operating Instructions Manual

Hide thumbs Also See for SINAMICS V20 Series:
Table of Contents

Advertisement

Commissioning
5.5 Quick commissioning
Parameter
Description
P2021[0]
MODBUS address
P2022[0]
MODBUS reply timeout
P2014[0]
USS / MODBUS telegram off time
5.5.1.4

Setting application macros

CAUTION
When commissioning the inverter, the application macro setting is a one-off setting. Make
sure that you proceed as follows before you change the application macro setting to a value
different from your last setting:
1. Do a factory reset (P0010 = 30, P0970 = 1)
2. Repeat the quick commissioning and change the application macro
Failure to observe may cause the inverter to accept the parameter settings from both the
currently and the previously selected macros, which may lead to undefined and
unexplainable operation.
Functionality
This menu defines certain common applications. Each application macro provides a set of
parameter settings for a specific application. After you select an application macro, the
corresponding settings are applied to the inverter to simplify the commissioning process.
The default application macro is "AP000" for application macro 0. If none of the application
macros fits your application, select the one that is the closest to your application and make
further parameter changes as desired.
Application
Description
macro
AP000
Factory default setting. Makes no parameter changes.
AP010
Simple pump applications
AP020
Simple fan applications
AP021
Compressor applications
AP030
Conveyor applications
52
Factory
Default for
default
Cn011
1
1
1000
1000
2000
100
Display example
The minus sign indicates that this macro is
the currently selected macro.
Remarks
MODBUS address for inverter
Maximum time to send reply back
to the master
Time to receive data
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167