Appendix C Services Gateway Environmental Specifications; Services Gateway Environmental Specifications; Table 29: Services Gateway Environmental Specifications - Juniper SRX 5600 Hardware Manual

Services gateway
Hide thumbs Also See for SRX 5600:
Table of Contents

Advertisement

Appendix C
Services Gateway Environmental
Specifications

Services Gateway Environmental Specifications

Services Gateway Environmental Specifications on page 183
Table 29 on page 183 specifies the environmental specifications required for normal
services gateway operation. In addition, the site should be as dust-free as possible.
For more information, see "Maintaining Hardware Components" on page 79.

Table 29: Services Gateway Environmental Specifications

Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE: Install the services gateway only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17,
and 110-18 of the National Electrical Code, ANSI/NFPA 70.
For additional safety guidelines and requirements, see "Safety and Regulatory
Compliance Information" on page 147.
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to
90%, noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
AC power: 11,322.8 BTU/hour (3,318 W)
DC power: 9,632 BTU/hour (2,823 W)
Services Gateway Environmental Specifications
183