SRX 5600 Services Gateway Hardware Guide
Removing an AC Power Supply
The power supplies are located at the rear of the chassis. Each AC power supply
weighs approximately 5.0 lb (2.3 kg).
CAUTION: Do not leave a power supply slot empty for more than 30 minutes while
the services gateway is operational. For proper airflow, the power supply must remain
in the chassis, or a blank panel must be used in an empty slot.
NOTE: After powering off a power supply, wait at least 60 seconds before turning it
back on.
To remove an AC power supply (see Figure 65 on page 135):
1.
2.
3.
4.
5.
6.
134
Replacing Power System Components
Switch off the dedicated facility circuit breaker for the power supply, and remove
the power cord from the AC power source. Follow the ESD and disconnection
instructions for your site.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and
connect the strap to one of the ESD points on the chassis. For more information
about ESD, see "Preventing Electrostatic Discharge Damage" on page 152.
Move the AC switch next to the appliance inlet on the power supply to the off
position (
O
).
Unscrew the captive screws on the bottom edge of the power supply.
Remove the power cord from the power supply.
Pull the power supply straight out of the chassis.