Replacing the SRX5600 Services Gateway Fan Tray
Removing the SRX5600 Services Gateway Fan Tray
To replace a fan tray, perform the following procedures in sequence:
1. Removing the SRX5600 Services Gateway Fan Tray on page 1
2. Installing the SRX5600 Services Gateway Fan Tray on page 2
NOTE: To prevent overheating, install the replacement fan tray immediately after
removing the existing fan tray.
To remove the fan tray (see Figure 1):
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and
1.
connect the strap to one of the ESD points on the chassis.
Loosen the captive screws on the fan tray faceplate.
2.
Grasp the fan tray handle and pull it out approximately 1 to 3 inches.
3.
WARNING: To avoid injury, keep tools and your fingers away from the fans as you
slide the fan tray out of the chassis. The fans might still be spinning.
Press the latch located on the inside of the fan tray to release it from the chassis.
4.
Place one hand under the fan tray to support it and pull the fan tray completely
5.
out of the chassis.
Replacing the SRX5600 Services Gateway Fan Tray
1