Juniper SRX 5600 Hardware Manual page 95

Services gateway
Hide thumbs Also See for SRX 5600:
Table of Contents

Advertisement

CAUTION: Do not mix AC and DC power supplies within the same device. Damage
to the device might occur.
To power on a DC-powered services gateway:
Verify that an external management device is connected to one of the Routing
1.
Engine ports (
AUX
,
CONSOLE
connecting management devices, see "Connecting the Services Gateway to
Management and Alarm Devices" on page 57.
Turn on the power to the external management device.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and
3.
connect the strap to one of the ESD points on the chassis. For more information
about ESD, see "Preventing Electrostatic Discharge Damage" on page 152.
Verify that the power supplies are fully inserted in the chassis.
4.
Verify that the source power cables are connected to the appropriate terminal:
5.
the positive (+) source cable to the return terminal (labeled
negative (–) source cable to the input terminal (labeled
Switch on the dedicated facility circuit breakers to provide power to the DC
6.
power cables.
7.
Check the
INPUT OK
LED is lit steadily green to verify that power is present.
If power is not present:
8.
Verify that the fuse is installed correctly and turn on the breaker at the battery
distribution fuse board or fuse bay.
Check the voltage with a meter at the terminals of the power supply for
correct voltage level and polarity.
Switch the circuit breaker on each of the power supplies to the
9.
and observe the status LEDs on each power supply faceplate. If a DC power
supply is correctly installed and functioning normally, the
and
INPUT OK
LEDs light green steadily.
If any of the status LEDs indicates that the power supply is not functioning
normally, repeat the installation and cabling procedures described in "Replacing
Power System Components" on page 133.
Chapter 9: Grounding and Providing Power to the Services Gateway
, or
ETHERNET
). For more information about
Powering On a DC-Powered Services Gateway
) and the
RETURN
48V
).
ON
position
,
,
PWR OK
BRKR ON
69