Table 5-4, Afcs General Troubleshooting - Garmin G1000 Nxi System Maintenance Manual

Hide thumbs Also See for G1000 Nxi:
Table of Contents

Advertisement

Annunciation
Condition
Aileron Mistrim Right
Aileron Mistrim Left
Rudder Mistrim Right
Rudder Mistrim Left
Pre-Flight Test Fails
Condition
Poor AP Performance
(Limited AP Authority)
AP DISC Problems
Loss of Manual Electric Trim
AutoTrim Inoperative
G1000 NXi System Maintenance Manual
King Air 300 Series
190-00716-N1
Resolution
Check for possible fuel imbalance.
Check aileron control adjustments.
If mistrim condition still exists remove and replace the roll servo.
Check rudder control adjustments.
If mistrim condition still exists remove and replace the yaw
servo.
Allow the system to complete pre-flight tests.
The preflight test should finish within 2 minutes. If it does not
pass, the red 'PFT' annunciation is shown. In case of PFT
failure, see Section 5.8.3 for additional PFT diagnostics.

Table 5-4, AFCS General Troubleshooting

Resolution
Check each servo gearbox slip clutch per Section 4.9. Verify the
clutches are not excessively loose and are within torque limits.
Check aircraft controls for proper balancing and adjustment per
the King Air 300 Series Maintenance Manual.
Check aircraft control cables for proper tension per the King Air
300 Series Maintenance Manual.
For intermittent nuisance disconnects with no AFCS of PFT alert,
check A/P disconnect switch and wiring for intermittent faults.
If an AFCS or PFT alert is displayed at the time of the disconnect,
troubleshoot per Section 5.8.
Check the GIA AFCS Fault Logs according to Section 5.8.2. If a
Mon Prmtr Invalid message is received, check for valid true
airspeed. A faulty GTP 59 OAT probe may cause TAS to become
invalid, which will flag the Mon Prmtr Invalid message.
Contact Garmin Product Support for assistance
Check pitch trim servo status.
Check MET switch discrete inputs to both GIAs by going to the
GIA I/O Configuration page and selecting DISCRETE IN inputs.
Check flap-in-motion discrete inputs to both GIAs for proper
operation by going to the GIA I/O Configuration page and selected
DISCRETE IN inputs. See Section 4.8.
If DATA indicator fails to illuminate or illuminates incorrectly,
troubleshoot flap motor & discrete input wiring (refer to G1000
Wiring Diagram, listed in Table 1-1,).
Page 171