M800W/M80W Series Connection and Setup Manual
4 General Specifications
Output conditions
Insulation method
Rated load voltage
Max. output current
Output delay time
(Note 1) When using an inductive load such as a relay, always connect a diode (voltage resistance
Source output
(Note 2) When the rush current exceeds the maximum output current, always connect a protective
Source output
CAUTION
1. When using an inductive load such as a relay, always connect a diode in parallel to the load to prevent a
counter-electromotive force.
2. When the rush current exceeds the maximum output current, always connect a protective resistor serially to
the load to suppress rush currents.
IB-1501268-K
100V or more, twice or more the load current) in parallel to the load.
24VDC
Inductive load
Y
Diode
resistor (R=150Ω) serially to the load to suppress rush currents. Make sure that the current is
less than the maximum output current including the momentary current.
24VDC
Load Resistor
Y
Optocoupler insulation
24VDC
2A/point
8A or less in the whole unit
400μs
Control
circuit
Control
circuit
142