4 General Specifications
(Note 1) When using an inductive load such as a relay, always connect a diode (voltage resistance 100V or
more, twice or more the load current) in parallel to the load.
Source output
(Note 2) When the rush current exceeds the maximum output current, always connect a protective resistor
(R=150Ω) serially to the load to suppress rush currents. Make sure that the current is less than the
maximum output current including the momentary current.
Source output
(Note 3) Always keep the total sum of output current of each Y200 to Y207, Y208 to Y20F, Y210 to Y217,
Y218 to Y21F, Y220 to Y227, Y228 to Y22F, Y230 to Y237 and Y238 to Y23F less than 0.8A.
Y 200
Y 201
Y 202
Y 203
Y 204
Y 205
Y 206
Y 207
Y 208
Y 209
Y 20A
Y 20B
Y 20C
Y 20D
Y 20E
Y 20F
CAUTION
1. When using an inductive load such as a relay, always connect a diode in parallel to the load to prevent a
counter-electromotive force.
2. When the rush current exceeds the maximum output current, always connect a protective resistor serially to
the load to suppress rush currents.
Inductive load
Y
Diode
Load Resistor
Y
0.2A or less per point
Y210
Y211
Y212
Y213
Total 0.8A
Y214
or less
Y215
Y216
Y217
Y218
Y219
Y21A
Y21B
Total 0.8A
Y21C
or less
Y21D
Y21E
Y21F
Y 220
Y 221
Y 222
Y 223
Total 0.8A
Y 224
or less
Y 225
Y 226
Y 227
Y 228
Y 229
Y 22A
Y 22B
Total 0.8A
Y 22C
or less
Y 22D
Y 22E
Y 22F
Total 3.8A or less
107
Y 230
Y 231
Y 232
Y 233
Total 0.8A
Y 234
or less
Y 235
Y 236
Y 237
Y 238
Y 239
Y 23A
Y 23B
Total 0.8A
Y 23C
or less
Y 23D
Y 23E
Y 23F
IB-1501268-K