Option
Holdup Delay
(0-999) Seconds
Fire Verify Delay
(0,120-255) Seconds
Here are some scenarios:
1st Trip
1st Trip
1st Trip
0 s
Sensor Inactivity
Time
(0-65535) Minutes
Fire Supervise Time
(120-65535)
Seconds
Burg Supervise Time
(120-65535)
Seconds
C
...
...
77
P/N 466-5227 • REVA • ISS 26AUG15
Default
0
120
Fire Alarm Verification Time = 120 seconds
No alarm
Restore
No restoral
Fire alarm reported
Restore
Reset
Power Up
13 s
40 s
0
14400
14400
The holdup delay is the duration in second that a holdup delay
sensor type will wait before it activates. If additional holdup
activations occur during the holdup delay period then the
holdup delay will immediately expire and set the holdup alarm.
If a holdup delay sensor type is de-activated during the holdup
delay period then the holdup alarm will reset and not activate.
The fire alarm verification feature is designed to reduce false
alarms reported by smoke detectors.
When a smoke sensor is first tripped, the ZeroWire will raise
an Action Event 'Smoke Power Reset'. For hard wired 4-wire
smoke detectors, you may program the output to follow the
action event and power-cycle the detector(s). Hard wired
sensors will be given 13 seconds to power-cycle.
The ZeroWire will wait 40 seconds to allow the smoke sensor
to power up and settle. If a second trip occurs after this but
before the end of the Fire Verify Delay time, a fire alarm will be
generated. If no restoral is received after the first trip, a fire
alarm will also be generated.
The valid time selection in this segment is 120 to 255 seconds.
The communicator will delay for a specified time before
reporting the fire alarm
2nd Trip
Fire alarm
Waiting for second trip
Sensors programmed with Sensor Inactivity in the Sensor
Options must be sealed and unsealed within the time
programmed here (in minutes). If they do not, a Sensor
Inactivity will report. This feature can be enabled in "System
Options". See section 4.5.
Default Sensor Inactivity option is off and this timer is set to
10080 minutes (7 days).
This applies only to wireless sensors programmed as fire type.
Sensors send a reduced packet count supervisory signal
every 60 minutes (check your sensor manual for most up to
date details). If no supervisory signal is received by the panel
within the time specified here then the sensor will be reported
as missing.
When set to 0 the default of 14,400 seconds (4 hours) will be
used. Check your local regulations for the correct value to use.
This applies only to wireless sensors programmed as non-fire
type. Sensors send a reduced packet count supervisory signal
every 60 minutes (check your sensor manual for most up to
date details). If no supervisory signal is received by the panel
within the time specified here then the sensor will be reported
as missing.
When set to 0 the default of 43,200 seconds (12 hours) will be
used. Check your local regulations for the correct value to use.
ZeroWire Reference Guide
Function
Fire alarm reported
Reset timer, wait for first trip
133 s
©2015 United Technologies Corporation
I
..
...
.. .
..