1 Action Number
The ZeroWire can support a total of 32 Actions. Each
Action is identified by a unique number, which cannot
be altered, and remains as the key reference for each
Action.
C
...
...
111
P/N 466-5227 • REVA • ISS 26AUG15
A c t i o n s S u b m e n u s
ZeroWire Reference Guide
2 Action Name
Each Action can be configured with a custom 32
character name. The name is displayed wherever
an Action is referenced on the ZeroWire system.
3 Function
Timed – The action state turns on for the time
specified.
Follow – The action state turns on once the
Event conditions have been satisfied, then off
once the Event conditions are not true.
On Delay – The action state becomes on
after the programmed time period unless
logic result is no longer active.
Off Delay – Follows the result of the logic
equation, but remains active for the time
programmed after the logic result is no longer
active.
On Pulse – Action state turns on for the
programmed time or the active period of the
logic result, whichever is the SHORTEST.
Latch – The action state stays on once the
Event conditions have been satisfied.