8.3

Connecting Peripheral Devices

Figure 8.1
illustrates how to configure the drive and motor to operate with various peripheral devices.
• Refer to the specific manual for the devices shown below for more detailed installation instructions.
Figure 8.1
Power
Supply
Molded Case
Circuit Breaker
(MCCB)
or
Electric Leakage
Circuit Breaker
(ELCB)
Magnetic
Contactor
(MC)
AC Reactor
Zero-phase
Reactor
Fuse
Input Side
Noise Filter
<1>
To obtain the driver and software of USB Copy Unit, CopyUnitManager and DriveWizardPlus, access the Yaskawa website at
http://www.yaskawa.com
Note: If the drive is set to trigger a fault output when the fault reset function is activated (L5-02 = 1), then a sequence to interrupt power
on a fault will shut off power to the drive when the drive attempts to restart. The default setting for L5-02 is 0 (fault output active
during restart attempt).
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
LED Operator/LCD Operator
USB Copy unit
<1>
(Type-AB, sold separately)
Surge
Absorber
Drive
+2
+1
DC Link
Choke
Ground
R/L1 S/L2
T/L3
U/T1V/T2W/T3
24 V control
power supply
unit
Output Side
Noise Filter
Magnetic
Contactor
(switches to
line power)
Figure 8.1 Connecting Peripheral Devices
8.3 Connecting Peripheral Devices
Engineering Software Tools
DriveWizard
USB Cable
(Type-AB)
PC
USB Cable
B1 B2
Thermal Relay
Braking Resistor Unit
Motor
Zero-phase
Reactor
Ground
<1>
+3
Braking Unit
Y E A _
T M o n
ly
315