Omron NT - SUPPORT TOOL FOR WINDOWS V4 Operation Manual page 477

Table of Contents

Advertisement

Data Conversion
Correction related to number of window/keyboard screens to be opened
Correction related to display range of window/keyboard screens
468
Status before
Conversion
With a conventional
With a new model,
model, a window/
a window/keyboard
keyboard screen is
screen is removed
specified as a child
from child screens.
screen.
When a window/keyboard screen is converted, conversion is executed as shown
below due to differences in number of window/keyboard screens that can be dis-
played at the same time.
S Difference
New models (NT21, NT31/631-V1 and above):
Conventional models, New models (NT31/631):
S Conversion result, error message and corrective action
Status before
Conversion
With a new model
Minimum value is
with "-V1" and
restored for window/
above, local window
keyboard screen
2 is specified for the
number.
attribute of touch
switch. And the
touch switch is reg-
istered to the sym-
bol manager.
When a window/keyboard screen is converted, conversion is executed as shown
below due to differences in the window/keyboard screen display range between
a conventional and a new model.
S Difference:
New models:
Status after
Error Message
Conversion
The screen no. XXX
of type YYY is not
supported as a
child, so the parent-
child association is
discarded.
Up to three window/keyboard screens can be opened
at the same time. (1 Global Window and 2 Local Win-
dows)
With a screen attribute, up to two local windows can
be specified as pop-up windows to be displayed
when the screen is opened.
With a touch switch (cursor move and input key-win-
dow/keyboard function), specification of local win-
dow 1 or 2 is possible.
Only one window/keyboard screen can be opened.
(Local window 1 (keyboard) only)
With a screen attribute, only one window can be spe-
cified as a pop-up window to be displayed when the
screen is opened.
With a touch switch (cursor move and input key-win-
dow/keyboard function), specification of only local
window 1 (keyboard) is possible.
Status after
Error Message
Conversion
Input Key-Window/
Keyboard screen
number is not within
the valid range.
Minimum value re-
stored.
A window/keyboard screen can be specified only in
the range that fits the touch switch grids.
Appendix A
Corrective Action
Copy the contents of the
window/keyboard
screen to a standard
screen and specify that
standard screen as a
child screen. (Refer to
5-3-2.Overlapping
Screens)
Corrective Action
Correct the screen data
so that the local window
1 includes all the re-
quired elements.