Recipe Table
Description of Parameter Setting Table Controls
Import
–32,768 or greater than 32,767, the value will be set to 0. Otherwise, if the sum of
Integer and Decimal digits exceed the maximum limit, the number of Decimal
digits will be reduced. For example, given a parameter with settings "Dec," "4 In-
teger" and "4 Decimal" and value 54.3675, when word size is reduced to 1, set-
ting will become "4 Integer" and "1 Decimal" and value will be 54.3.
When entering values into the Integer and Decimal fields, the following validation
will occur. When "Dec/Hex" is decimal and "Integer" or "Decimal" is set so that
their sum is greater than the maximum digits allowed, once the cell loses the fo-
cus, the following occurs:
a) If the entered value is less than or equal to the maximum digits allowed, it is
accepted. Any other value is reduced, so that their sum is not greater than the
maximum digits allowed.
b) Otherwise, the entered value is set to the maximum digits allowed and the oth-
er value is set to 0.
The maximum digits allowed is 5 (1 word) or 10 (2 words).
No.
Displays the parameter entry number.
Parameter
Displays the parameter name.
A string of up to 8 characters can be used and edited.
Dec/Hex
Displays the numeral display format, either decimal or hexadecimal.
When this is changed Integer and Decimal will be reset to default.
Sign
Display sign option. Check if you want a sign to be displayed.
Integer/Decimal
Displays the precision of the integer/decimal digit of the numeral data. Limitation
on the sum of integer and decimal digits will follow the numeral display restriction.
Words
Defines the memory size for the parameter. The address column will be reset
when this size is changed.
PLC Address
Displays the starting PLC address used by the parameter.
Goto Entry
This will allow the selection of an entry by specifying the entry number through a
Go to dialog.
Insert Mark
Inserts a mark object in a parameter name.
The Parameter values in the records of a recipe can be edited through a CSV
(Comma Separated Values) file. Each line consists of the fields of a record, with a
comma separating two fields.