System Information Settings
5-6-9

CSV File Auto-save Settings

Error Check Capacity
when Saving Files
If Set auto-save of CSV file is selected, the following screen will be dis-
played.
Set the amount of disk space at which to generate an alarm or error when the
drive in which the CSV file is being saved starts becoming full. Setting the val-
ues as megabytes. An alarm or error will be generated when the drive set to
save the CSV file in for Trend Screens reaches the specified level or lower.
Set the disk space within the following ranges for an alarm or error to be gen-
erated.
Disk space for generating an alarm: 10 to 5,000 MB (Default: 1,000 MB)
Disk space for generating an error: 1 to 4,999 MB (Default: 100 MB)
The CX-Process Monitor Plus does not provide functions to delete or over-
write old files.
Note
Although different drives can be set for the Trend Screens, the error and alarm
settings are used for all of them.