Example Function Blocks for Data Exchange
1,2,3...
70
3-2 Monitoring a Contact (Bit)
Example: Monitoring the Basic PID block's High MV Limit Output (MHA) from
Monitor Plus
The following steps are required to monitor a bit's status.
1. Use the Contact Distributor (Block Model 201) to temporarily store the
function block's bit status in the Loop Control Unit or Board's memory.
2. Use the Internal Switch (Block Model 209) to read the temporarily stored
data from memory and write it to the CPU Unit's data area.
3. Set the tag for Monitor Plus (used to monitor the bit from Monitor Plus) in
the Internal Switch's bit. In this case, S2's tag name is set to MHA.
Set tags for Monitor Plus.
(Select Display to read data.)
Loop Control Unit or Board
Contact
Function
Distributor
block
(Block
Model 201)
Function
block
Actual Setting Procedure
The following settings are used to monitor a bit's status from Monitor Plus.
Monitor Plus
CPU Unit
I/O memory
Internal
Switch
(Block
Model
209)
Section 3-2
Specify the tags
for Monitor Plus
and write data.