3. Parameters screen:
Figure 5–18. Ind Sqrt type point programming: Parameters screen
a. Input Scales block: Refer to step 3a in the Linear type point
b. Output Scales block: Refer to step 3b in the Linear type point
c. Filter: Refer to step 3c in the Linear type point programming
d. Current: Refer to step 3d in the Linear type point programming
4. Alarm Limits screen: Refer to Similar Programming Parameters section
for instructions.
5. Press Apply.
The dry contact point type allows a point to be programmed to detect an
Dry Contact
open or closed contact. Programmable parameters for dry contact point
types are nearly identical to those for linear point types.
1. Display Scale screen:
programming section.
programming section. Note that the Low Scale Output entry is
not programmable.
section.
section.
Point Programming
Programming
SV100A/SV10AC User Guide
5-17