Thermo Fisher Scientific
1. Type screen: Select Moving Average > Next.
Figure 5–27. Moving Average Calculated type point programming: Type screen
2. Display Scale screen: Refer to the Similar Programming Parameters
section for instructions.
3. Parameters screen:
Figure 5–28. Moving Average Calculated type point programming: Parameters
screen
a. Base Point: Moving average calculations must be performed on
another point. This point is referred to as the base point. To
establish the base point, press the Base Point input box and type in
the base point number.
b. Time Period (min): This is the length of time in which values are
averaged. Enter the time in minutes. Maximum length of time is
1440 minutes.
c. Press Next.
4. Alarm Limits screen: Refer to the Similar Programming Parameters
section for instructions.
Point Programming
Programming
SV100A/SV10AC User Guide
5-27