Thermo Scientific SmartView SV100A User Manual page 82

100mm paperless data acquisition system
Table of Contents

Advertisement

Point Programming
Programming
5-24
SV100A/SV10AC User Guide
3. Parameters screen:
Figure 5–24. High-Low Difference Calculated type point programming;
Parameters screen
a. First Point and Last Point: The high-low difference point is the
average of the first and last points. For example, within the range of
points assigned to the Hi-Lo difference point type, if the highest
point data value is 100 and the lowest is 90, the high-low difference
data will be 10. Press the First Point/Last Point boxes, and enter
the point number.
b. Press Next.
c. Alarm Limits screen: Refer to the Similar Programming Parameters
section for instructions.
d. Press Apply.
 Totalize: The totalize calculation keeps a running total of the value of a
point sampled at a programmed rate. This continues until the
programmed reset interval time, at which time the value is logged to
the Alarm/Event Summary, reset to zero, and the totalization
calculation begins again. However, a low flow cutoff provision prevents
totalization on flow rates that fall below the cutoff point.
1. Type screen: Select Totalize > Next.