Ind Sqrt - Thermo Scientific SmartView SV100A User Manual

100mm paperless data acquisition system
Table of Contents

Advertisement

Point Programming
Programming
5-16
SV100A/SV10AC User Guide
b. Display Block: Refer to the Similar Programming Parameters
section for instructions. Note the following differences:
 Major/Submajor/Minor Grids: Not programmable. Grids are
 Decimal Fix: Not programmable. Log points displayed as base
c. Press Next.
3. Parameters screen: Refer to step 0 in the Linear type point
programming section to program the input scales, output scales, filter,
and/or current. Press Next to continue.
4. Alarm Limits screen: Refer to the Similar Programming Parameters
section for instructions.
5. Press Apply.

Ind Sqrt

Use this function for inputs requiring the Industrial Square Root of the
input signal. The square root of the percentage of input scale is calculated
and then multiplied by the high end scale to produce the value of the point
displayed. In the following example, the input is 4–20 mA, low end scale =
0, and high end scale = 1000:
Square
root
of
1. Type screen: Refer to step 1 in the Linear type point programming
section.
2. Display Scale screen: Refer to the Similar Programming Parameters
section for instructions.
fixed based on the number of log scale decades.
10 exponentials.
High
end
scale
Input
signal
12
mA
or
0
.
5
0
.
707
0
.
707
1000
gal
.
/
min
.
50
%
of
scale
equal
to
1000
707
gal
.
/
min
.
0
.
5
(
decimal
fix
0
).
Thermo Fisher Scientific