c. Default Gateway: This is the IP address that is used when
communicating with other devices on a different network. The
address is a 32-bit value normally expressed with four values (0 to
255) separated by a period. The default setting is 0.0.0.0. Set this
value according to the system or the network to which the recorder
belongs. In some cases this setting may not be needed.
d. SV100A FTP Config Client Login Block: You can set up the
recorder to accept INI (configuration) files from a host computer.
This section allows you to safeguard this feature by entering the
user name with a password.
e. TCP/Modbus Floating Point Format: Select the type of Modbus
floating point format that the recorder's communications uses: 1 x
32 float format maps the point data into a single 32-bit register,
while the 2 x 16 float format maps the point data into two
consecutive 16-bit registers. This setting should match your host
communications protocol dealing with floating point values.
f. Web Server Port: The default port (end point) for web services is
80. For example, if the port is set to 80, you would enter
"http://10.209.64.137:80" in the browser address field. The web
server port can be set to any port from 1 through 65535.
2. Press Next.
3. FTP Server Login screen: This screen allows you to set up the recorder
to access a server. You can set the recorder to automatically transfer
data and alarm/event files to a predetermined place on the primary
server. If the primary server is down, the recorder attempts to transfer
the files to the secondary server if one is programmed.
Figure 7-5. FTP Server Login screen
a. Auto Transfer: Press Yes to enable the function and enter the time
the transfer should occur by pressing the Hour input box. Enter the
transfer time (programmable in whole hours only).