Table 18: Description Of Marking Example For Approved I/O Module Ex I According To Atex And Iecex; Table 20: Description Of Marking Example For Approved I/O Module Ex I; Table 21: Description Of Marking Example For Approved I/O Module Ex I - WAGO 750 Manual

16do 24vdc 0.5 a, low-side switching 16-channel digital output module 24 vdc; low-side switching
Table of Contents

Advertisement

42
Use in Hazardous Environments
Table 18: Description of Marking Example for Approved I/O Module Ex I According to ATEX and
IECEx
Marking
TUEV 12 ATEX 106032 X
IECEx TUN 12 0039 X
Dust
II
3 (1) D
Ex
tc
[ia Da]
IIIC
T135°C
Dc
Mining
I
M2 (M1)
Ex
d
[ia Ma]
I
Mb
Gases
II
3 (1) G
Ex
ec
[ia Ga]
IIC
T4
Gc
Pos : 78.9 /All e Seri en ( Allgemei ne Module)/Ü bers chriften/Ebene 3/Kennz eichnung für die Verei nigten Staaten von Ameri ka (NEC) und Kanada (CEC) - Ü bers chrift 3 @ 29\mod_1495099368853_21.doc x @ 422071 @ 3 @ 1
Manual
Version 1.1.0
750-1505 16DO 24VDC 0.5 A, low-side switching
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22) equipment containing a safety
device for a category 1 (Zone 20) equipment
Explosion protection mark
Type of protection: Protection by enclosure
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 20
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment Group: Mining
Category: High level of protection with electrical
circuits which present a very high level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
electrical circuits
Explosion group for electrical equipment for mines
susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Explosion protection mark
Equipment protection by increased safety "e"
Type of protection and equipment protection level
(EPL): Associated apparatus with intrinsic safety
circuits for use in Zone 0
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)
Public
WAGO I/O System 750

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-1505