4. If applicable, configure the filter time for the signals of the digital inputs.
5. If applicable, configure the device check for validation and backup.
6. If applicable, configure pin 2 by setting the I/Q behavior.
7. If applicable, enter the expected vendor ID.
8. If applicable, enter the expected device ID.
9. If applicable, set the expected cycle time.
10. Click the [Apply] button.
ð Your changes now take effect.
Configuring the Operating Mode for Pin 4 of the Port
You can select the port operating mode for pin 4 of the selected IO-Link port from the
Port mode drop-down list. The following operating modes are available:
Table 59: "Port Mode" Drop-Down Menu: Selecting the Operating Mode for Pin 4 of the Selected IO-Link Port
Selection Option
Deactivated
IOL Manual
IOL Autostart
Digital input, normally
open
Digital input, normally
closed
Digital Output
Digital output, static on
Setting the Filter Time for Digital Inputs
The filter time for the digital inputs can be selected from the Digital input signal filter
drop-down menu. You can select from the following values:
• No digital input filter
• 3 ms
• 15 ms
• 20 ms
If the No digital input filter option is selected, no filtering occurs.
Configure Pin 2 (I/Q)
The behavior of pin 2 (I/Q) can be selected from the IQ behavior drop-down menu. For
your IO-Link class A device, the following configuration options are available for using
pin 2 as a digital input or output:
Selection Option
Not supported
Digital input, normally
open
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
Description
The port is disabled. L+ is switched off. The process data (both input and output) is
set to 0. The master no longer performs actions related to this port.
The port is used as an IO-Link port with manual (user-defined) configuration. The
vendor ID, device ID and version ID are validated.
The port is used as an IO-Link port with automatic start. No configuration or device
validation occurs.
The port is used as a digital input. All elements of the port configuration are ig-
nored except for the input and output data length.
The port is used as a digital input. The signals to the port are inverted. All elements
of the port configuration are ignored except for the input and output data length.
The port is used as a digital output. All elements of the port configuration are ig-
nored except for the input and output data length.
The port is used as a digital output. The signal on pin 4 is permanently set to
logic 1 (for testing purposes only).
Table 60: IQ Behavior Drop-Down Menu – Configuration of Pin 2 (I/Q) for IO-Link Class A Devices
Explanation
Pin 2 is not used.
Pin 2 is a digital input.
Commissioning