Table 52 "Port Mode" Drop-Down Menu: Selecting The Operating Mode For Pin 4 Of The Selected Io-Link Port - WAGO 765-4203/0100-0000 Product Manual

4-port io-link master class a; ethercat; 24 v dc; 2.0 a; 4 x m12 connection
Table of Contents

Advertisement

Commissioning
Name
VendorID
DeviceID
The Validation and Backup, PortCycleTime, VendorID and DeviceID settings only ap-
pear for the IOL Manual selection in the Port mode (pin 4) drop-down menu.
Changes to settings require operator or admin rights. If you do not have these, the Con-
figuration tab is grayed out, and the displayed values cannot be edited.
If cyclic data exchange takes place via PROFINET, no configuration is possible. In this
case, a message appears:
Note: Changing configuration not allowed because interface state
is "communicating."
To makes changes to a port's configuration, proceed as follows:
1. Select the desired port (port X01, port X02 etc.) from the menu
2. Open the Configuration tab.
3. Configure pin 4 by setting the port operating mode.
4. If applicable, configure the filter time for the signals of the digital inputs.
5. If applicable, configure the device check for validation and backup.
6. If applicable, configure pin 2 by setting the I/Q behavior.
7. If applicable, enter the expected vendor ID.
8. If applicable, enter the expected device ID.
9. If applicable, set the expected cycle time.
10. Click the [Apply] button.
ð Your changes now take effect.
Configuring the Operating Mode for Pin 4 of the Port
You can select the port operating mode for pin 4 of the selected IO-Link port from the
Port mode drop-down list. The following operating modes are available:
Table 52: "Port Mode" Drop-Down Menu: Selecting the Operating Mode for Pin 4 of the Selected IO-Link Port
Selection Option
Deactivated
IOL Manual
IOL Autostart
Digital input, normally
open
Digital input, normally
closed
Digital Output
Digital output, static on
74
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Type
Description
Input field
Expected manufacturer ID of the connected device
Input field
Expected device ID of the connected device
Description
The port is disabled. L+ is switched off. The process data (both input and output) is
set to 0. The master no longer performs actions related to this port.
The port is used as an IO-Link port with manual (user-defined) configuration. The
vendor ID, device ID and version ID are validated.
The port is used as an IO-Link port with automatic start. No configuration or device
validation occurs.
The port is used as a digital input. All elements of the port configuration are ig-
nored except for the input and output data length.
The port is used as a digital input. The signals to the port are inverted. All elements
of the port configuration are ignored except for the input and output data length.
The port is used as a digital output. All elements of the port configuration are ig-
nored except for the input and output data length.
The port is used as a digital output. The signal on pin 4 is permanently set to
logic 1 (for testing purposes only).