Mitsubishi Electric MELDAS 600M Series Instruction Manual page 500

Table of Contents

Advertisement

4.5 Operation warnings (OPW
No.
OPW0101 Auto operation
OPW0102 Single block stop
OPW0103 Verify stop
OPW0104 External
OPW0105 Internal interlock
OPW0106 Operation mode
OPW0107 No operation
OPW0108 Operation mode
OPW0109 Cutting override
OPW0110 Rapid feed
Downloaded from
ManualsNet.com
CHAPTER 4 APPENDICES
Appendix 4. Warning Messages
Message
The automatic operation
pause signal ON
stopped because the automatic
operation stop signal turned ON.
The block stopped because the
signal ON
single block stop signal turned
ON.
The operation is in a compare
stop state.
The external interlock function
interlock axis
has been validated and one of
exists
the axes has entered the
interlock state.
The servo OFF function is valid.
Or, an axis in an axis removal
axis exists
state was commanded.
The automatic operation mode
change
changed to another automatic
operation mode during
operation.
Starting was attempted without
mode
selecting the operation mode.
Or, canceling of the operation
mode was attempted during
operation.
Starting was attempted with
duplicated
duplicated operation modes, or
another duplicating operation
mode was selected during
operation.
The cutting feed override switch
zero
on the machine operation panel
is set to "0".
The "RAPID TRAVERSE
override zero
OVERRIDE" switch on the
machine operation panel is set
to "0".
search engine
)
Details
• The operation can be restarted by
canceling the automatic operation
stop signal.
• Restarting will cause one block to
be executed and then the block
will stop. Canceling the single
block stop signal and starting will
cause continuous operation.
• Restarting will cause the
continuous operation to restart.
• Cancel the interlock signal.
• Cancel the servo OFF signal.
• Cancel the command.
• Return to the original automatic
operation mode, and restart.
• Restart after selecting the
operation mode.
• Restart after selecting the
operation mode.
• Set the switch to a value other
than "0" to cancel the error.
• If the switch is set to a value other
than "0", check for a short circuit
in the signal wire.
• Check the sequence program.
• Cancel the error by setting the
"RAPID TRAVERSE OVERRIDE"
switch to a value other than "0".
• If the "RAPID TRAVERSE
OVERRIDE" switch is set to a
value other than "0", check for
short-circuits in the signal wire.
• Check the sequence program.
IV – 58