Installation
AC Input Wire
The manufacturer recommends the AC input wire specified in Table 2-2 and Table
2-3. This must be permanently connected to an approved AC distribution box with
suitably rated over-current protection. If you require a special cord, contact the
manufacturer.
Table 2-2 AC Wire Specification for 6000 Watt Units
AC Input Voltage Range
190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)
342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)
f
Table 2-3 AC Wire Specification for 12000 Watt Units
AC Input Voltage Range
190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)
342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)
2–8
Wire
4 x 10 AWG (3 wire plus safety ground), stranded
°
copper, 60
C minimum, 300V, 0.800 in.
maximum cable diameter, rated for 25A.
4 x 14 AWG (3 wire plus safety ground), stranded
°
copper, 60
C minimum, 600V, 0.800 in.
maximum cable diameter, rated for 13A.
Wire
4 x 6 AWG (3 wire plus safety ground), stranded
°
copper, 60
C minimum, 300V, outside diameter
(OD) of cable is ≤ 1 in., rated for 50 A.
4 x 10 AWG (3 wire plus safety ground), stranded
°
copper, 60
C minimum, 600V, outside diameter
(OD) of cable is ≤ 1 in., rated for 25 A.
TM-XDOP-01XN