Table 2.2 Operational AC Input Voltage Ranges and Frequency
AC Voltage Range
85-130 Vac 1
190-264 Vac 1
1. 6 V model: 95-130 Vac
AC Fail LED The AC Fail (ACF) LED turns on when the input voltage is outside
of the range specified for the power supply. The LED turns off when the input
voltage is within the range.
AC Input
Cord
WARNING
The AC input cord is the disconnect device for the power supply. The plug must
be readily identifiable by and accessible to the operator. The input cord must be
no longer than 9.84 feet (3 m).
The AC input cord we recommend is specified in Table 2.3, "AC Wire
Specification". Add a non-locking plug suitable for use in the country in which you
are operating. If you require a special cord, call us.
Table 2.3 AC Wire Specification
Wire Size
3 x 12 AWG stranded copper
3 x 16 AWG stranded copper
1.
Alternate choice for 190-264 Vac input only.
AC Input Wire
1. Strip the outside insulation on the AC cable approximately 4 in. (100 mm). Trim
Connection
the wires so that the ground wire is 0.5 in. (12 mm) longer than the other wires.
Strip 0.55" (14 mm) at the end of each of the wires. See Figure 2.2 detail (top).
2. Unscrew the base of the strain relief from the helix-shaped body. Insert the base
through the outside opening in the AC input cover and, from the inside, screw
the locknut securely onto the base.
Release 3.1
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
(20 A maximum at 120 Vac)
φ
(12 A maximum at 230 Vac)
φ
Ratings
60 °C minimum, 300 V 0.545-0.708 in.
1
60 °C minimum, 300 V 0.545-0.708 in.
AC Input Power Connection
Frequency
1
47-63 Hz
47-63 Hz
Cable Outside Diameter
(13.63-17.7 mm)
(13.63-17.7 mm)
Installation
41