Table C-14 Auto Sequence Commands - Xantrex XDC 10-1200 Operating Manual

Xdc 6000 watt and 12000 watt series digital programmable dc power supply
Hide thumbs Also See for XDC 10-1200:
Table of Contents

Advertisement

Table C-14 Auto Sequence Commands

Function
SCPI Command
Delete selected
[:]PROGram[<channel>][:SELected]:DELete[:SELect
sequence
ed]
Delete all sequences [:]PROGram[<channel>][:SELected]:DELete:ALL
Select a sequence to
[:]PROGram[<channel>][:SELected]:NAME
run or edit
<sequence_number>
Change Auto
[:]PROGram[<channel>][:SELected]:STATe
Sequence operating
{RUN|PAUSe|STOP}
state
Skip to the next step
[:]PROGram[<channel>][:SELected]:STEP:NEXT
(while running in
auto sequence)
Read selected
[:]PROGram[<channel>][:SELected]:COUNt?
sequence number of
steps
Delete selected
[:]PROGram[<channel>][:SELected]:STEP<step_numb
sequence step
er>:DELete
Exit a selected
[:]PROGram[<channel>][:SELected]:EXIT
sequence
Read current step
[:]PROGram[<channel>][:SELected]:STEP:EXECuting
number
?
Edit selected
[:]PROGram[<channel>][:SELected]:STEP<step_numb
sequence step
er>[:EDIT]
[[[[[<voltage>],<current>],<power>],<OVP_level>
],{<time>|TRIG}]
Insert step into
[:]PROGram[<channel>][:SELected]:STEP<step_numb
selected sequence
er>:INSert
[[[[[<voltage>],<current>],<power>],<OVP_level>
],{<step_time|TRIG}]
Program selected
[:]PROGram[<channel>][:SELected]:STEP<step_numb
sequence step
er>:CURRent <current>
current
Description
The selected sequence is deleted
All sequences are deleted
Select sequence to run or edit
Change operating state of current
auto sequence
Skip to start of next step. Error if
STATe is not RUN
Read number of programmed
steps in selected sequence
Delete the selected sequence step
Exit a selected sequence
Query current step in execution
Edit the selected sequence step
Insert a step into the selected
sequence
Edit/program step current of
selected sequence
Query
N/A
N/A
Yes
Yes
N/A
Yes
N/A
N/A
N/A
Yes
N/A
Yes

Hide quick links: