Xantrex XDC 10-1200 Operating Manual page 201

Xdc 6000 watt and 12000 watt series digital programmable dc power supply
Hide thumbs Also See for XDC 10-1200:
Table of Contents

Advertisement

1
30 Minute Drift
8 Hour Drift Temperature Stability
Temperature Coefficients
Analog Programming Interface
1. At 25°C ±5°C, with full power load
2. At 25°C ±5°C after 30 minutes full load operation
TM-XDOP-01XN
Voltage
0.04% of Vmax
Current
0.6% of Imax
Power
6000W: 1% of Pmax
12000W: 2% of Pmax
2
Voltage
0.02% of Vmax
Current
6000W: 0.04% of Imax
12000W: 0.05% of imax
12000W 600V model: 0.08% of Imax
Power
0.1% of Pmax
Front Panel or Remote Digital Interface
Voltage Programming
Current Programming
Power Programming
Voltage Readback
Current Readback
Power Readback
Remote Analog Programming Interface
Voltage Programming
Current Programming
Voltage Readback
Current Readback
Programming Lines, Impedance
0-5 V
range
>30 kOhm
dc
0-10 V
range
>30 kOhm
dc
Readback Lines, Impedance
0-5 V
range
<500 Ohm
dc
0-10 V
range
<1 kOhm
dc
Isolation, all program and readback lines
58 Vdc with respect to chassis potential
Output Performance Specifications
0.04% of Vmax/°C
0.06% of Imax/°C
0.1% of Pmax/°C
0.04% of Vmax/°C
0.06% of Imax/°C
0.1% of Pmax/°C
0.04% of Vmax/°C
0.06% of Imax/°C
0.04% of Vmax/°C
0.06% of Imax/°C
A–9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents