Canbus Error Codes; Multichannel Error Codes; Table D-11 Canbus Error Codes; Table D-12 Multichannel Error Codes - Xantrex XDC 10-1200 Operating Manual

Xdc 6000 watt and 12000 watt series digital programmable dc power supply
Hide thumbs Also See for XDC 10-1200:
Table of Contents

Advertisement

Error Messages

CANbus Error Codes

Table D-11 CANbus Error Codes

Error code Error Message Description
+1701
+1702
+1703
+1704
+1705
+1706

Multichannel Error Codes

Multichannel functionality is only available with the 6000 Watt power supply.

Table D-12 Multichannel Error Codes

Error code Error Message Description
+1800
+1802
+1803
+1804
+1805
D–8
CANbus hardware missing
The CANbus option is not installed on the controller card, or controller card
is not present.
CANbus device specific error
An error has occurred on the CANbus circuit. Probable causes are AC input
too low, AC input not secure, controller card not securely fastened or other
noise sources.
CANbus input buffer corrupted.
CANbus input buffer corrupted.
CANbus input buffer overrun.
Data is sent on the CANbus faster than the CPU can process.
CANbus output buffer overrun.
Data cannot be transmitted fast enough.
Multichannel general error
An error has occurred while sending multichannel commands. One such
cause is sending a command that is too long.
Multichannel address taken
The multichannel address configured for this unit has already been assigned
to another unit on the CANbus network.
Multichannel originator not responding
The originator of the message is not responding to the handshaking.
Multichannel recipient not responding
The recipient of the message is not acknowledging the reception of the
command.
Multichannel command overwritten
A received command through the CANbus has been overwritten.
TM-XDOP-01XN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents