Xantrex XDC 10-1200 Operating Manual page 74

Xdc 6000 watt and 12000 watt series digital programmable dc power supply
Hide thumbs Also See for XDC 10-1200:
Table of Contents

Advertisement

Operation
To set the Over-Current Protection:
Step # Do This
1
2
3
4
5
6
7
To set the Under-Current Protection:
Step # Do This
1
2
3
4
5
6
7
3–12
PROT SET
ALARMS
Press repeatedly until the
PROT SET
ALARMS
desired setting appears.
ENTER
Use the Current knob, the numeric
keypad, or the arrow keys to enter a
value (0–103% of the unit's rated
current).
ENTER
Use the arrow keys to select Yes or No.
For this example, Yes is selected.
ENTER
PROT SET
ALARMS
PROT SET
Press repeatedly until the desired setting
ALARMS
appears.
ENTER
Use the Current knob, the numeric keypad, or the
arrow keys to enter a value. The value must be
between 0–103% of the unit's rated current.
ENTER
Use the arrow keys to select Yes or No. For this
example, Yes is selected.
ENTER
You Will See
OVP SET 0V
OCP SET 0A
OCP SET 0A
OCP SET ####A
S/D if trip? N
S/D if trip? Y
This setting is saved and the display
returns to its default operating mode.
You Will See
OVP SET 0V
UCP SET 0A
UCP SET 0A
UCP SET ####A
S/D if trip? N
S/D if trip? Y
This setting is saved and
the display returns to its
default operating mode.
TM-XDOP-01XN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents